
Use your browser's back button to return to the main Heat Wheel page.
AIRotor DDC/Speed Control
On/Off Control
The AIRotor will receive power and will operate when the main disconnect
is turned on. The DDC controller supplied with the unit controls the AIRotor
as indicated below. The AIRotor can be turned on and off remotely by removing
the jumper between terminals W1 and W2 and providing a remote dry contact.
Rotation Detection
A magnet fitted to the periphery of the rotor actuates a pulse sensor once
every revolution. If the drive belt should fail, in 20 minutes the dry contacts
will close between terminals W5 and W6, sending a signal to a remote alarm
furnished by others.
Automatic Purge
When wheel is at minimum signal or zero recovery, the wheel will automatically
run at minimum speed for 10 seconds every 30 minutes to ensure that the rotor
surface is kept clean.
Gentle Starting
The control unit soft-starts the wheel, taking approximately 30 seconds to
ramp up the wheel to maximum speed. This extends the life of the drive and
belt.
TEMPERATURE CONTROLS (XeteX DDC Control)
AIRotor DDC Temperature Controller
The speed of the AIRotor is controlled by the furnished DDC control which
supplies a 0-10VDC signal to terminals #W1 (+) and #W3 (-). The DDC controller
modulates the speed of the AIRotor for the following functions.
Frost Control
When the exhaust temperature (T-EA) leaving the AIRotor falls below the recommended
setpoint of 15oF, the rotor speed is reduced to reduce heat recovery and maintain
a minimum exhaust temperature.
Maximum Discharge Temperature Speed Control
The remote modulating signal shall modulate the speed of the rotor to maintain
a maximum Supply Air discharge temperature leaving the AIRotor (T-SA). As
T-SA rises above the setpoint of 58oF, rotor speed is reduced to decrease
rotor effectiveness. If T-SA is below setpoint, the rotor runs at maximum
speed with maximum recovery.
Summer Mode Control
When the Outside Air temperature (T-OA) rises above the return air temperature
(T-RA), the rotor should be run at maximum speed for maximum recovery.
AIRotor Control (Speed Control Signal by Others)
On/Off Control
The AIRotor will receive power and will operate when the main disconnect is
turned on. A modulating signal is required to control the AIRotor speed. The
controller can be set up for the following input signals: (0-5V, 0-10V, 1-5V,
2-10V, 5-10V, 10-0V, 10-2V, 10-5V, 0-20V Phase cut, 0-20mA, and 4-20mA). The
AIRotor can be turned on and off remotely by removing white jumper from terminals
#5 and #6 in wheel speed control panel and connecting remote switch as indicated.
Rotation Detection and Alarm
A magnet fitted to the periphery of the rotor actuates a pulse sensor
once every revolution. Under normal operation the internal contacts are in
the energized position (contact closed between #15 and #13). If the drive
belt should fail or if the drive stops, after 20 minutes the internal contacts
shall close between #15 common and #14 NC), sending a signal to a remote alarm
furnished by others.
Automatic Purge
When wheel is at minimum signal or zero recovery, the wheel will automatically
run at minimum speed for 10 seconds every 30 minutes to ensure that the rotor
surface is kept clean.
Gentle Starting
The control unit soft-starts the wheel, taking approximately 30 seconds to
ramp up the wheel to maximum speed. This extends the life of the drive and
belt.
RECOMMENDED TEMPERATURE CONTROLS (Control Signal by Others)
Maximum Discharge Temperature Speed Control
The remote modulating signal shall modulate the speed of the rotor to maintain
a maximum Supply Air discharge temperature leaving the AIRotor (T-SA). As
T-SA rises above the recommended setpoint of 58 F, rotor speed is reduced
to decrease rotor effectiveness. If T-SA is below setpoint, the rotor runs
at maximum speed with maximum recovery.
Summer Mode Control
When the Outside Air temperature (T-OA) rises above the return air temperature
(T-RA), the rotor should be run at maximum speed for maximum recovery.
Frost Control
When the exhaust temperature (T-EA) leaving the AIRotor falls below the recommended
setpoint of 15oF, the rotor speed is reduced to reduce heat recovery and maintain
a minimum exhaust temperature.
Use your browser's back button to return to the main Heat Wheel page.
| Home
| Air Displacement | Energy
Recovery |
| Company Profile | Contact
XeteX | Site Map |
© XeteX, Inc.
612-724-3101
info@xetexinc.com