Total Energy Recovery for a School Addition
This unit provides total energy recovery and outdoor air ventilation for a school. The heat wheel unit transfers both heat and humidity, keeping the indoor space dry in the summer and maintaining a comfortable moisture level in the winter. With its integral gas fired furnace, this unit satisfies all the air conditioning needs for the students and instructors.
Performance Specification
- Model: AVR–2250–HI
- Supply cfm: 15,650
- Exhaust cfm: 13,130
- Built: July, 2004
- Weight: 8,000 lbs
- Energy Recovered: 927 MBH (Winter), 305 MBH (Summer)
- Design Conditions: -10° F / 47% RH (Winter), 90° F / 45% RH (Summer)
Unit Features
- AIRotor Series–R, RXA 2250 Hygroscopic Rotary Total Energy Recovery Exchanger
- 33” Heavy Duty, Spring Isolated, Backward Inclined Airfoil Plenum Blowers with NEMA Frame ODP, Premium Efficiency Motors
- Heavy Duty Double Wall (18 ga / 22 ga), 2" Thick Fiberglass Insulated, Galvanized Steel Cabinet
- Outside Shutoff and Exhaust Backdraft Dampers
- 813 Mbtu Indirect (Tube) Gas Fired Furnace
- 2" MERV 8 (30/30) Outside Air and Return Air Filters
- Configured for Indoor installation
- ETL Listed