Rep Login
school ventilation
The unit is equipped with removable access doors due to space restrictions.

Super Efficient Energy Recovery for School Ventilation

This unit uses a double-pass flat plate heat exchanger for super-efficient energy recovery, achieving an effectiveness of 76%. The hot water coil provides the necessary make-up heating during the coldest winter periods providing fresh air conditioned outdoor air year-round to the students and staff.

Performance Specification

  • Model: XVS–40–XD–42–BP–HW
  • Supply cfm: 5,500
  • Exhaust cfm: 5,500
  • Built: July, 2006
  • Weight: 3,500 lbs
  • Energy Recovered: 312 MBH (Winter), 91 MBH (Summer)
  • Design Conditions: 3° F / 50% RH (Winter), 96° F / 37% RH (Summer)

Unit Features

  • XLT–40–42 Aluminum, Double-Pass, Flat Plate Heat
  • 15" Forward Curved DWDI Fans Driven by NEMA Frame, ODP, Premium Efficiency Motors, Vibration Isolated, with Adjustable Sheaves
  • Heavy Duty Double Wall (18 ga / 22 ga), 1" Thick Fiberglass Insulated Galvanized Steel Cabinet; Welded Structural Steel Frame with Lifting Lugs
  • Outside Air Shut-Off, Exhaust Air Shut-Off, and Outside Air Face-and- Bypass Dampers
  • 270 MBH Hot Water Coil
  • 2" MERV 8 (30/30) Outside Air and Return Air Filters
  • Configured for Indoor installation
PDF file download.
Powered by: Avallo Panel